We have been able to offer a wide range of premium M-Swift drive batteries to our valued customers. These batteries are purchased from reliable and reliable suppliers in the industry, to ensure high quality standards. Their constant performance, environmentally friendly design and long backup make these batteries very popular on the market.
Model |
TITAN 5000 |
TITAN 7500 |
TITAN 10000 |
TITAN 15000 |
TITAN 20000 |
TITAN 30000 |
|
Capacity |
5000VA / 4000 Watts |
7500VA / 6000 Watts |
10000VA / 8000 Watts |
15000VA / 12000 Watts |
20000VA / 16000 Watts |
30000VA / 24000 Watts |
|
Output wave form |
Pure sine wave |
||||||
Input |
SINGLE PHASE INPUT , SINGLE PHASE OUTPUT (2 WIRE SYSTEM WITH GROUND, 220V NOMINAL, 50 Hz) |
THREE PHASE INPUT( 415VAC NOMINAL , 50 Hz, 4 WIRE SYSTEM WITH GROUND), SINGLE PHASE OUTPUT |
|||||
Inverter Mode |
|||||||
Undervoltage cut off |
130V+-10VAC |
||||||
Overvoltage cut off |
280V+-10VAC |
||||||
|
|
|
|||||
Output |
On battery |
220V +/- 10% |
|||||
On mains |
Same as input |
||||||
|
Frequency on battery |
50 Hz +/- 0.1 Hz |
|||||
|
Frequency on mains |
Same as input |
|||||
|
Overload alarm starts at load |
4000W |
6000W |
8000W |
12000W |
16000W |
24000W |
|
UPS trips at load |
6000W |
10000W |
12000W |
18000W |
24000W |
36000W |
No of times UPS will turn on & off before dropping the load |
5 |
ZERO |
|||||
|
Over load Protection |
On Battery : Internal current limiting : On mains: MCB protection |
On Battery : Internal current limiting : On mains: 3 Phase MCB Protection |
||||
|
Switchover Time |
20 ms |
|||||
|
Total No of Outlets |
HT-3 BAKELLITE SOCKET |
|||||
|
Cold Start |
Yes |
|||||
Battery |
DC BusVoltage |
96V OR 120V |
180V DC |
360VDC |
|||
|
Number of batteries |
8 OR 10 |
15 |
30 |
|||
|
Battery (Ah) Max |
UPTO 180 AH |
|||||
Battery type |
Lead acid battery or Tubular Battery |
||||||
Battery low alarm |
10.6V +/- 0.2 |
||||||
|
Battery low cut off voltage |
10.2+-0.2V |
|||||
|
Float charging voltage |
|
|||||
|
a. Low charge mode |
13.5 V +-0.1V |
|||||
|
b. High charge mode |
13.7V+- 0.1V |
|||||
|
Boost Charging Voltage |
14.1 V+0 0.1V |
|||||
Charger capacity |
|||||||
a. Low charge mode |
7.5A +/- 1.A |
||||||
|
b. High charge mode |
10A +- 2 A |
|||||
|
Protection |
Battery Deep discharge,overcharge, overload, short circuit |
|||||
|
|
|
|||||
Communications & Management |
Visual indicators |
LED 7 SEGMENT DISPLAY SHOWING MAINS AC, UPS, LO BAT, OVERLOAD. HENCE LEDs ARE NOT REQUIRED |
COMBINATION OF LED INDICATORS AND OPTIONAL LCD METERS |
||||
|
Audible alarms |
Onbattery, Low battery, Over load, Fault, Cold Start |
Onbattery, Low battery, Over load, Fault |
||||
|
|
|
|||||
Physical |
Unit Dimensions (D * W * H) Max in mm |
540x320x550 |
800x450x880 |
||||
|
Nett Weight (Kg's) Max |
45 |
60 |
70 |
105 |
120 |
140 |
|
Shipping Dimensions (L * W * H) Max |
620x400x640 |
920x570x1000 |
||||
|
Shipping Weight (Kg's) Max |
55 |
70 |
80 |
120 |
140 |
160 |
Environment |
Operating temperature |
0 - 50 degree C |
|||||
|
Operating humidity |
0 - 95% |
|||||
|
Storage temperature |
from -10 to 70 degree C |
|||||
|
Storage humidity |
0 - 95% Non Condensing |