Range |
300 V – 460 V AC 50 Hz 3 PH |
Other Input Ranges |
245 V- 460 V AC 3Ph |
340 V- 460 V AC 3Ph |
|
360 V- 460 V AC 3Ph |
|
other ranges as per customer requirement |
|
Frequency |
47Hz to 53 Hz |
Output Voltage |
380 V / 400 V/ 415 V AC 3Ph 50 Hz |
System |
Unbalanced 4 Wire : R Y B N |
Connections |
Star |
Output Voltage Adjustable |
380 V to 415 V AC in 3Ph |
220 V to 240 V AC in 1Ph |
|
Output Voltage Regulation |
± 1% |
Over Load Capacity |
120% |
Correction Rate |
15 V / 20 V / 35 V / Sec-1Ph |
25 V / 35 V / 60 V / Sec-3Ph |
|
110V/Sec for D.C. Motor controlled |
|
Waveform Distortion |
Nil |
Output Waveform |
True Reproduction of Input |
Insulation |
Class 'B' |
Short CKT Period & percentage |
300 % for 250 m.sec. |
Normal Operating Temperature |
0ºC to 45ºC |
Climatic Conditions |
90 % RH.Max.Non-Condensing at 35º C |
Mode of System |
Fully Automatic / Manual |
System Construction |
AS PER IS : 9815 of 1994 |
More details:View company website