Additional Details
Overview Totally configurable safety module monitors numerous safety devices such as E-stop buttons, interlocking switches, safety light screens, two-hand controls and rope pull switches. 22 input terminals can monitor both contact-based or PNP solid-state outputs from Banner devices or any other manufacturers Each input can be a non-safety input, or configured for Control Reliability or Category 2, 3 or 4 safety circuit performance per ISO 13849-1 3 pairs of solid-state safety outputs rated at 0.75A each (24V dc) with selectable one- or two-channel external device monitoring and ON-delay or OFF-dalay 10 configurable auxiliary status outputs track inputs, outputs, lockout, I/O status and other functions Easy configuration with built-in front panel LCD display or PC Interface Live Display and a Fault Log provide real-time system and fault history identification Controller is designed to meet stringent standards including Safety Integrity Level (SIL) 3 per IEC 62061 and IEC 61508, and Category 4 Performance Level (PL e) per ISO 13849-1