The relay consists of separately detecting the voltage across each of the fuses. Under normal conditions, the potential across the fuses is close to zero. By opening the fuse, the potential increases from one fuse to another. This potential drives the current through the LED of the optocoupler. The optocoupler is on because of the current in the optocoupler provides the path of the circuit for the external LED indication and also for the electromagnetic relay. The detection circuit comprising the optocoupler and the associated driving circuit is separated for each phase. However, the electromagnetic relay providing potential-free contacts for alarm and control is common for all 3 phases.
Features:
Solid state reliability
High-speed operation
Very high load impedance operation
Application:
The relay monitors the health of PT fuses.
Ratings:
Load impedance:
Load impedance between phases should not be more than 20K Ohms
Operating time:
Less than 10 milliseconds between the opening of fuse and closing of the open contact of electromagnetic relay
Ordering Information:
Rated voltage: 110V AC, 50Hz. 3 phases
Relay Type: JRV 123
Auxiliary power supply: 20 to 60V DC, 75 to 150V AC / DC, 175 to 300V DC / 185 to 250V AC
With almost more than a decade of experience and rich technological expertise, we are able to offer a precision designed range of Electrical Protection Instruments.