The relay measures the line current from each of the phases and if it exceeds the set threshold, then relay extends a trip signal after an operating time. The relay's operating time is determined by selecting one of the four inverse time characteristics. The relay has facility to active / inhibit the high set protection feature. The relay output contacts are self reset . Relay operation without any fault current is determined by trip test facility.
Features:
Software based design
Programmable time current characteristics
Choice of four curves
Selectable characteristic angle
Programmable directional / Non-directional element
Draw - out case
Application:
The relay provides time graded phase and earth fault protection of Parallel transformers, Transformer feeders, Parallel feeders, ring main system etc.,
Settings:
Operating characteristics:
1) 3.0s Normal Inverse
2) 1.3s Normal Inverse
3) 1.5s Very Inverse
4) 0.8s Extremely Inverse
Phase O/c (IDMT): 50 to 200% in steps of 10%
Earth fault (IDMT): 5 to 80% in steps of 5%
TMS: 0.1 to 1.0 in steps of 0.01 (separate for O/c & E/F)
Phase Hi-set : 200 to 3200% in steps of 200%
Earth fault Hi-set: 50 to 800% in steps of 50%
Burden:
Current input :
0.2VA per phase (rated 5A)
0.05VA per phase (rated 1A)
Aux. Supply:
Less than 8W (Non operated)
Less than 10W (Operated)
Contacts Durability:
Loaded contact : 10,000 operations min.
Unloaded contact : 100,000 operations min.
Char. Angel setting
O/C setting: Lead 30º / Lead 45º /Lead 60º
E/F setting : Lag 12.5º / Lag 30º / Lag 45º
Ratings:
Aux. Supply :
1) 20 to 60V DC
2) 75 to 175V AC / DC
3) 175 to 300V DC
185 to 250V AC
Rated Voltage : OVER CURRENT 110V AC / EARTH FAULT 63.5V AC