Our online ups for machinery are offered in various specifications, these are quality tested for accuracy and power consumption before being supplied to our clients.
RATING |
1,2,3,4,5,6,7.5 & 10 KVA |
7.5,10 & 20KVA |
30,40,50,60,80 KVA |
|
SINGLE PHASE INPUT/ OUTPUT |
1PH INPUT/OUTPUT & |
3PH INPUT / 3 PH OUTPUT |
INPUT |
|||
RECTIFIER DESIGN |
IGBT BASED ACTIVE PFC PWM RECTIFIER |
||
|
140 - 290 V AC (140 - 160 25% LOAD > 160 100% LOAD) |
145 V AC (-20% TO 15% ) 3PH & N |
|
NORMAL FREQUACY |
50HZ ± 10% |
||
INPUT POWER FACTOR |
≥ 0.99 |
≥ 0.9 |
≥ 0.8 |
BATTERY(KVA) |
1 2 3 5 6 7.5 10KVA |
7.5 10,15,20 KVA |
30,40,50,60,80 KVA |
VOLTAGE(VOLT) |
36-96 96-240 120-240 192-240 240 240 240 |
192-240 240-360 |
360 |
OUTPUT |
|||
INVERTER DESIGN |
IGBT BASED PWM WITH DSP CONTROLLED |
||
DC-AC EFFICIENCY |
82 TO 92% (BASED ON DC VOLTAGE & UPS RATING ) |
90% |
|
VOLTAGE |
230±1% |
230±1% |
400±1% |
FREQUENCY |
50 HZ + IN SYNCHRONOUS MODE, 50HZ + 0.1 HZ FREE RUNNING MODE |
50 HZ ± 0.1 % |
|
THD |
≤ 2 % ON LINEAR LOAD & ≤ 5% ON NON - LINEAR LOAD |
||
CREST FACTOR |
3:1 |
||
OVERLOAD |
150 % FOR ONE MINUTE, 120 % FOR TEN MINUTES |
||
PROTECTION |
BATTERY LOW/HIGH O/P LOW / HIGH, SHORT CIRCUIT, BUILT IN SPIKE SURGE & RFI / EMI FILTER |
||
INDICATION |
MAINS, INVERTER, UPS ON BATTERY, BATTERY LOW, INVERTER TRIP, O/P OVERLOAD, LOAD ON UPS, BYPASS |
||
MEETING |
LCD, GRAPHICS DISPLAY TO MONITOR O/P, I/P , DC VOLTAGE, LOAD % FREQUENCY, BATTERY, BATTREY HEALTH |
||
BYPASS |
MANUAL / AUTO (BI - DIRECTIONAL) |
MANUAL / AUTO |
|
COMMUNICATION |
RS - 232 SERIAL INTERFACE / SNMP (OPTIONAL) |
||
ENVIRONMENT |
NOISE LEVEL - LESS THAN 60 DBA, TEMPERATURE - 0.45 C, HUMIDITY - 0.95 % NON- CODENSING |
||
TESTING STANDARDS |
ICE 62040 - PART - III |