Welcome to Pepagora.com, Join FreeSign In

CPM 700 (Continuous Particulate Monitoring)

Continuous particulate monitoring 700 series monitors are advanced detection devices that measure changes in particulate concentration.

  • FOB Price
    NA
  • Min Order Quantity
    NA
  • Payment Terms
    NA
  • Share:
Request for Quote

Other Details

Description for CPM 700:

          Continuous particulate monitoring 700 series monitors are advanced detection devices that measure changes in particulate concentration. Using a unique emissions detection technique, CPM 700 series instruments maintain calibration because they are less affected by dirty or misaligned optics, or a faulty light source often found in other type detectors. Bha offers two models in this product series: the standard CPM700, and the more advanced cpm 750.

Features and benefits of CPM 700:

1. Emissions detection technique - self-compensating, no drift, low maintenance .
2. Span/zero check with automatic check cycle.
3. Three stage alarm systems.
4. Ambient light detection - automatically detects and offsets for ambient light.
5. Adjustable damping - smoothes the response to rapid fluctuations in emissions.
6. Led bar graph display.
7. Additional feature on the cpm 750 model
Analog output- allows the connection of external equipment.

Technical Specifications

General:

Measuring principle:dynamic, transmission, scintillation.Measuring range: minimum range 0-50 mg/m3Accuracy: 1% full scaleConformity:(cpm 750): ce, tuv, ta air, 13. Bimschv, u.S. Epa

Transmitter head:

Material: 6061 aluminum
Protection: nema-4x
Power input: 15 vdc from the cpm 700/750 receiver head.
Air purge connection: 1/4 in. (6.35 mm)
Purge air requirements: minimum 5 psi above duct pressure
Weight: 6.6 lbs. (3.0 kg)
Light source: light emitting diode
Temperature range: Process: 10 F to 350 F (-12 c to 177 c)
ambient: 10 F to 135 F (-12 c to 57 c)

Receiver head / electronics:

Material: Steel
Protection: nema type 4, 12
Power input: 100-240 vac, 50/60 hz
Air purge connection: 1/4 in. (6.35 mm)
Purge air requirements: minimum 5 psi above duct pressure
Hardware alarm relays: Four
Relay type:dry contact
Relay operating range: 2A @ 0-250 VAC or 0-24 VDC
Analog output: one, 4-20 mA (CPM 750)
Dimensions: 8 x 10 x 4 in. (203 x 254 x 175 mm)
Weight: 11.8 lb. (5.4 kg)Minimum
Duct Width: 3 in. (76.2 mm)
Maximum Duct Width: 20 ft. (6 meters)
Supplied Interconnecting Cable: 50 ft. (15 meters)
Temperature range: Process: 10 F to 350F (-12° C to 177° C)
ambient: 10 F to 135F (-12° C to 57° C).

Images